Smart-UPS On-Line 230 V
Unity output power factor single-phase, double-conversion online UPS with advanced management features
The Smart-UPS On-Line 230 V is a single-phase, double-conversion online UPS with advanced management features. This UPS provides high density, true double-conversion on-line power protection. It has a capacity of 3000VA/2700W and offers scalable runtime while minimizing maintenance. The 2U rackmount SRT comes with a preinstalled Network Management Card in the Smart Slot for UPS network-based monitoring and management. Additionally, it includes British, IEC C20, and Schuko CEE 7/EU1-16P inputs, 8x IEC C13, 2x IEC C19 outlets, and 2x IEC jumpers. The UPS has a 3-year warranty, and the built-in lead-acid battery has a 2-year warranty. Its dimensions are 635mm (depth) x 85mm (height) x 432mm (width) and it weighs 31.30kg. This UPS is suitable for servers, voice/data networks, medical labs, and light industrial applications. It conforms to CE, CE Mark, EAC, EN/IEC standards, RCM, and VDE. The UPS is designed for IT professionals or network administrators, providing a wide input voltage window, tight output voltage regulation, frequency regulation, internal bypass, and input power factor correction.

Specifications
Presentation | High density, double-conversion on-line power protection with scalable runtime. |
Lead time | Usually in Stock |
Main | |
Run time for load | 2700 W |
Min-max load | 270-2700 W |
Run time at max load | 3min 58s |
Max. Capacity Used | 100 % |
Main Input Voltage | 230 V |
Product type | Uninterruptible power supply (UPS) |
Other Input Voltage | 220 V, 240 V |
Main Output Voltage | 230 V |
Other Output Voltage | 220 V, 240 V |
Rated power in W | 2700 W |
Rated power in VA | 3000 VA |
Input Connection Type | BS1363A British, IEC 60320 C20, Schuko CEE 7 / EU1-16P |
Output Connection Type | 8 IEC 60320 C13, 2 IEC Jumpers, 2 IEC 60320 C19 |
Number of rack units | 2U |
Cable length | 2.44 m |
Number of cables | 1 |
Provided equipment | CD with software, Documentation CD, Installation guide, Network management card, Rack mounting brackets, Rack mounting support rails, USB cable, Warranty card |
Batteries & Runtime | |
Battery type | Lead-acid battery |
Number of battery filled slots | 1 |
Battery recharge time | 3 h |
Number of battery replacement | 1 |
Battery voltage | 96 V |
Battery charger power | 168 W rated |
Battery life | 3…5 year(s) |
Replacement battery | APCRBC152 |
Extended runtime | 1 |
General | |
UPS type | Double conversion online |
Product web sub-family | High density |
Number of power module free slots | 0 |
Number of power module filled slots | 0 |
Redundant | No |
Physical | |
Colour | Black |
Height | 8.5 cm |
Width | 43.2 cm |
Depth | 63.5 cm |
Net weight | 31.3 kg |
Mounting location | Front |
Mounting preference | Lower |
Mounting mode | Rack-mounted |
Two post mountable | 0 |
USB compatible | Yes |
Mounting position | Horizontal |
Input | |
Network frequency | 40...70 Hz auto-sensing |
Input voltage limits | 100...275 V adjustable (half load) |
Output | |
Maximum configurable power in VA | 3000 VA |
Maximum configurable power in W | 2700 W |
Output frequency | 50/60 Hz +/- 3 Hz sync to mains |
Wave type | Sine wave |
Harmonic distortion | Less than 2 % |
Crest factor | 3 : 1 |
Bypass type | Internal bypass (automatic and manual) |
Additional information | Configurable for 220 : 230 or 240 nominal output voltage |
Conformance | |
Product certifications | CE, EAC, RCM, VDE |
Marking | CE Mark |
Standards | EN/IEC 62040-1:2019/A11:2021, EN/IEC 62040-2:2006/AC:2006, EN/IEC 62040-2:2018 |
Environmental | |
Operating temperature | 0…40 °C |
Relative humidity | 0…95 % non-condensing |
Operating altitude | 0...10000 ft |
Storage temperature | -15…45 °C |
Storage relative humidity | 0…95 % non-condensing |
Storage altitude | 0.00…15240.00 m |
Acoustic level | 55 dBA |
Heat dissipation | 703 Btu/h |
IP degree of protection | IP20 |
Communications & Management | |
Free slots | 0 |
Preinstalled device | Network management card 3 with environmental monitoring |
Alarm | Audible and visible alarms : prioritized by severity |
Emergency power off | Yes |
Surge Protection and Filtering | |
Surge energy rate | 340 J |